Monthly Fire Alarm Visual Inspection
What NFPA 72 §10.5 actually requires of building staff between formal inspections — monthly visual checks on panel, devices, and battery status.
What §10.5 requires monthly.
- Visual inspection of the fire alarm control panel display — normal status, no trouble lights, no supervisory signals.
- Visual inspection of remote annunciators if installed.
- Confirmation that the panel's primary AC power is on and the battery state is normal.
- Visual confirmation that visible smoke detectors are not painted over, blocked, or obstructed.
- Visual confirmation that pull stations are accessible.
- Confirmation that strobes are not blocked or obscured.
- Log entry in the building's compliance binder.
What Tyrian provides for the monthly check.
Standardized monthly visual checklist — printable PDF, takes a facility team member 10-15 minutes per inspection cycle. Log entry template that lives in the compliance binder. Trouble-condition escalation tree (when to call Tyrian for a service event vs. when to wait for the next quarterly visit).
Monthly inspection FAQs.
Can building staff do this if they're not NICET-certified?
Yes — §10.5 visual inspection is a non-certified scope. The quarterly and annual technical inspections require NICET credentials.
What if the panel shows trouble during the monthly check?
Call Tyrian. We respond to trouble conditions before they become deficiencies.
Is the monthly log audited?
AHJ inspectors review the building compliance binder; missing monthly logs are flagged.
Does Tyrian's quarterly visit substitute for the monthly check?
No — §10.5 monthly is in addition to §14 quarterly + annual.