Pittsburgh PLI Fire Alarm Inspection
What Pittsburgh PLI (Permits, Licenses & Inspections) actually reviews on a commercial fire alarm — submittal expectations, inspection-tag checks, common flags.
What Pittsburgh PLI reviews.
- Inspection-tag presence and currency inside the panel cabinet.
- Current §10.18 Record of Inspection in the building's compliance file.
- Design-submittal compliance for new construction and major retrofit (NICET IV / PE stamp).
- §14.4.4 quarterly battery-test documentation.
- Coverage compliance against the approved drawings — §17 detection, §18 notification.
- Elevator recall functionality on buildings with elevators.
- Mass notification / voice evac where occupancy class requires it.
Common PLI flags.
Missing or stale inspection tags. §10.18 records that show annual-only with no quarterly entries. Coverage drift from approved drawings after tenant build-outs. Elevator recall not demonstrated. POTS-line monitoring on a sunsetting AT&T circuit.
Tyrian and PLI.
Tyrian maintains ongoing relationships with Pittsburgh PLI inspectors and re-introduces on each new building. Audit-grade §10.18 reports are formatted for PLI review. Pre-submittal conversations on engineered design where the project supports.
Pittsburgh PLI FAQs.
Does PLI require NICET IV on design submittals?
PLI expects NICET IV or PA-licensed PE stamp on engineered fire alarm design drawings.
How often does PLI inspect existing buildings?
PLI compliance walks vary; routine occupancy reviews, complaint-driven inspections, and permit-driven reviews all occur.
What does PLI want to see in the compliance file?
Current §10.18 Record of Inspection, §7.5 Record of Completion, inspection tags. The audit-grade binder.
Where is this in the broader Pittsburgh code page?
Full Pittsburgh AHJ code guide at /code/pittsburgh-fire-alarm-code/.