Elevator Recall and the Fire Alarm System
Where NFPA 72 §21.3 elevator recall meets ANSI A17.1 — how detectors in elevator lobbies and machine rooms trigger recall, and what AHJs require.
What elevator recall is.
When a smoke detector activates in an elevator lobby (any floor) or in the elevator machine room or shaft, the elevator car automatically returns to a designated landing (typically the lobby), opens its doors, and stays there. Phase I recall. NFPA 72 §21.3 specifies which detectors trigger which recall sequences.
Alarm side vs. elevator side.
Alarm side (Tyrian’s scope): smoke detector installation in lobbies and machine rooms, panel programming, addressing, supervisory wiring to the elevator controller relay. Elevator side (elevator contractor’s scope): the elevator controller’s recall programming, the designated-landing logic, the firefighter-service Phase II features. Coordination is essential.
Common deficiencies.
Detectors installed but not wired to the elevator recall relay. Wired but never tested at acceptance. Tested at acceptance but the trip-test annotation didn’t make it into the §10.18 record. Machine-room detector that drifts out of compliance over time. Each is preventable with audit-grade documentation and coordinated commissioning.
Elevator recall FAQs.
Does Tyrian coordinate with the elevator contractor?
Yes — required for commissioning. The relay interface is the handoff point.
AHJ tests this at acceptance?
Yes — Phase I recall is a standard line item on the AHJ acceptance walk.
Does Tyrian inspect elevator recall on annual ITM?
The alarm-side detectors and panel programming, yes. Elevator-side annual inspection is the elevator contractor’s scope.
What's Phase II?
Firefighter-controlled operation — elevator key-switch override. Elevator contractor’s scope.